M-XF Series | Safety Excess Flow Valves

GVS® MXF valves provide instant shut-off in the event of a line break, preventing the release of hazardous or flammable products to the area which could result in a disastrous fire or explosion that could harm personnel, equipment, and the environment.

GVS® Malema valves

As the fluid enters the valve, it flows through the orifice to the outlet. The orifice and tapered piston create a venturi effect, accelerating the flow through the valve. At a preset flow rate, the pressure differential offsets the spring-loading of the piston and shuts off the valve. Fluid can flow through the valve in either direction, however, the flow will be shut off in the direction indicated on the valve. Adjustment is achieved by means of an externally adjustable screw that positions the piston closer or farther away from the orifice. Turning the adjusting screw clockwise to reduce the flow area causes actuation at lower preset flows.

All LPG tank cars and transport trucks are required by law to have excess flow valves installed. In addition, state LPG regulatory bodies require excess flow valves on all LPG storage vessels storing products for domestic delivery and consumption.

  • Fuel lines
  • Pollution control
  • Chemical processing
  • Gas and hydraulic lines
  • Petroleum and gas installations

Pollution control
Fuel lines
Chemical processing
Gas and hydraulic lines
Petroleum and gas installations
HOW IT WORKS
Play Video

Features

In-line repairable

repair or inspection without removal of body from pipeline

Effective operation

Liquids or gases

In-line flow

Available in sizes

From 3/4” to 12"

Broad calibration range

ANSI classes

From 150 to 2500

Cut-Away Illustration

Cut-Away-illustration
Cut-Away-illustration

The mounting position for this excess flow valve is horizontal. These valves can also be mounted vertically; this will change trip settings by approximately 15% (this is easily corrected since one can adjust the valve to counter for this change). The valve can be easily maintained in the field without removing from the pipeline as all of the components slide out of the top upon disassembly.

how it works

Cut-Away-illustration

Valve Open = Normal Flow

Cut-Away-illustration

Line Break = Flow Shut-Off

Built-in Reset Valve

Reset mechanism is integrated to the excess flow valve which has several advantages:

  • Eliminates additional piping and hardware required in upstream of the valve
  • Reduces the cost of installation.
  • Ease of installation.

How Reset Valve Works

Execution of below steps will result in valve reset because of equalized pressure on the both sides of valve:

  • Close the isolation valves in both sides of excess flow valve (upstream and downstream) on the pipeline
  • Open the isolation valve on the upstream side of the excess flow valve
  • Open the built-in reset valve on the bypass line of excess flow valve
  • Pressure equalization on both sides of the valve will cause the reset of the excess flow valve (valve opens)
  • Open the downstream isolation valve
  • Close the built-in reset valve on the bypass line of excess flow valve

Additional Accessories

OPEN/CLOSE indication can be provided with a use of differential pressure gauge.

Remote OPEN/CLOSE contact signal can be provided with a use of differential pressure switch.

A combination of built-in reset with above features is also available as an option which is useful for integrating with safety shutdown systems and other control strategies.

SPECIFICATIONS

specs Air Pressure at 14.7 psig & temperature at 70° F

Ordering Code

specs NOTE: Additional valve sizes and materials are available upon request
  • 0. No built-in reset valve
  • 1. Built-in reset valve
  • 2. Built-in reset valve with DP gauge
  • 3. Built-in reset valve with DP switch
  • 4. Built-in reset valve with explosion proof DP switch

Standards

Valve design per ASME B16.34 Flanged and Butt Weld ends are in accordance with ASME B16.5 and B16.25 Socket Weld and Threaded ends are in accordance with ASME B16.11 Flange dimensions are in accordance with ASME B16.5 Manufactured per: ISO 9001: 2015: Cert.no 0052985-01